CONTROL OPERATING SEQUENCE / UNIT COMPONENTS
Upon a call for heat from the thermostat, power is supplied to
the power exhauster motor. The unit will go through a purge
period and then the direct spark igniter will be energized. At the
same time, the main valve in the combination control valve will
open to allow gas to flow to the burners. If the fan motor has
not already started it will start shortly. If a flame is not sensed
within 7 seconds for any reason the main valve will close and
there will be a short purge period before ignition is tried again.
If the flame is not sensed after four tries there will be at least a
one hour wait before ignition is tried again.
CONTROL OPERATING SEQUENCE
Figure 15.1 - Major Gas, Electrical Service, Safety
and Other Components
1. Power Exhauster
2. Pressure Switch
3. Integrated Direct Spark
Control Board
4. Combination Gas Control
5. Control Transformer
5
2
1
4
3
7
8
8
6
9
10
6. Flame Sensor (hidden)
7. Auto Reset Limit Control (hidden)
8. Direct Spark Igniter (hidden)
9. Gas Pipe Connection
10.HorizontalAirDeectorBlades
Table 15.1 - Gas Controls - All Models
Table 15.1 - Propeller Unit Model PTP General Performance Data
Ratings shown are for elevations up to 2,000'. For
elevations above 2,000', ratings should be
reduced at the rate of 4% for each 1,000' above
sea level. (In Canada see rating plate.) Reduction
of ratings requires use of a high altitude kit.
Data taken at 55°F air temperature rise. At 65°F
ambientandunitredatfull-ratedinput.Mounting
height as measured from bottom of unit, and
withoutdeectorhoods.Forunitsequippedwith
deectorhoods,seepage16.
All motors used are produced, rated and tested by
reputable manufacturers in accordance with
NEMA standards and carry the standard warranty
of both the motor manufacturer and Modine. All
motors are totally enclosed and all single phase
motors have built-in thermal overload protection.
GENERAL PERFORMANCE DATA - MODEL PTP
Model PTP Sizes
150 175 200 250 300 350 400
Btu/Hr Input
150,000 175,000 200,000 250,000 300,000 350,000 400,000
Btu/Hr Ouput
120,000 140,000 160,000 200,000 240,000 280,000 320,000
Entering Airflow (CFM) @
70°F
2140 2725 2870 3995 4545 5280 5995
Outlet Velocity (FPM)
711 607 643 721 824 748 851
Air Temp. Rise (°F)
53 48 52 47 50 50 51
Max. Mounting
Height (Ft.)
15 14 15 18 19 18 21
Heat Throw (Ft.) (@
Max Mtg Ht)
51 50 53 62 69 65 74
Motor Type
PSC PSC PSC PSC PSC PSC PSC
Motor HP
1/6 1/6 1/3 1/3 1/2 1/2 3/4
Motor RPM
1075 1075 1075 1075 1075 1125 1125
Control System Description
Gas
Type
Control
Code
Control
Voltage
Service
Voltage
Single-Stage, Direct Spark
Ignition, 100% Shut-off with
Continuous Retry
Utilizes a single-stage
combination gas control with
ignition control.
Gas is lit with a direct spark
igniter on call for heat.
Natural 11
24V 115V
Propane 21
Two-Stage, Direct Spark
Ignition, 100% Shut-off with
Continuous Retry
Utilizes a two-stage combination
gas control with built-in ignition
control. Firing rate is 100% and
50% of full rated input. Gas is lit
with a direct spark igniter on call
for heat.
Natural 12
Propane 22